# variable speed drive ATV71- 18.5kW-25HP- 480V- EMC filter-graphic terminal -IP54

- Link: https://danfossexpress.com/product/variable-speed-drive-atv71-18-5kw-25hp-480v-emc-filter-graphic-terminal-ip54/
- Published: 2026-02-16T15:59:47+00:00
- Author: drivesexperts

## variable speed drive ATV71- 18.5kW-25HP- 480V- EMC filter-graphic terminal -IP54

**Manufacturer:** Telemecanique

**Part Number:** ATV71WD18N4

**EAN:** 3389119405751

### Key Specifications

 |  **Range of product** |  Altivar 71 |  
 |  **Motor power kW** |  18.5 kW, 3 phases at 380…480 V |  
 |  **Motor power hp** |  25 hp, 3 phases at 380…480 V |  
 |  **power supply voltage** |  380…480 V – 15…10 % |  
 |  **Network number of phases** |  3 phases |  
 |  **Line current** |  37.5 A for 480 V 3 phases 18.5 kW / 25 hp | 45.5 A for 380 V 3 phases 18.5 kW / 25 hp |  
 |  **Apparent power** |  29.9 kVA at 380 V 3 phases 18.5 kW / 25 hp |  
 |  **Nominal output current** |  34 A at 4 kHz 460 V 3 phases 18.5 kW / 25 hp | 41 A at 4 kHz 380 V 3 phases 18.5 kW / 25 hp |  
 |  **Maximum transient current** |  61.5 A for 60 s 3 phases 18.5 kW / 25 hp | 67.7 A for 2 s 3 phases 18.5 kW / 25 hp |  
 |  **Output frequency** |  0.1…599 Hz |  
 |  **Nominal switching frequency** |  4 kHz |  
 |  **Switching frequency** |  1…16 kHz adjustable | 4…16 kHz with derating factor |  
 |  **power supply voltage limits** |  323…528 V |  
 |  **power supply frequency** |  50…60 Hz – 5…5 % |  
 |  **power supply frequency limits** |  47.5…63 Hz |  
 |  **Output voltage** |  <= power supply voltage |  
 |  **type of cable for mounting in an enclosure** |  With a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC | With an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC | Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC | Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR |  
 |  **Minimum switching current** |  3 mA at 24 V DC for configurable relay logic |  
 |  **Maximum switching current** |  R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4 | R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4 | R1, R2: 5 A at 250 V AC resistive load, cos phi = 1 | R1, R2: 5 A at 30 V DC resistive load, cos phi = 1 |  
 |  **Frequency resolution** |  Analog input: 0.024/50 Hz | Display unit: 0.1 Hz |  
 |  **Net weight** |  31 kg |  
 |  **IP degree of protection** |  IP54 |  
 |  **Package 1 Weight** |  40.0 kg |

### Downloads

 * [📥 User guide](https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=ATV61-71_to_ATV600-900-340_Modernization_manual_EN_EAV64336_02.pdf&p_Doc_Ref=EAV64336)