# Variable speed drive, Altivar Process ATV900, ATV960 High Performance Drive System, 630/500kW, 400V, CE, IP23

- Link: https://danfossexpress.com/product/variable-speed-drive-altivar-process-atv900-atv960-high-performance-drive-system-630-500kw-400v-ce-ip23/
- Published: 2026-02-16T15:44:43+00:00
- Author: drivesexperts

## Variable speed drive, Altivar Process ATV900, ATV960 High Performance Drive System, 630/500kW, 400V, CE, IP23

**Manufacturer:** Schneider Electric

**Part Number:** ATV960C63Q4X1

**EAN:** 3606481276131

### Key Specifications

 |  **Range of product** |  Altivar Process ATV900 |  
 |  **Colour of enclosure** |  Light grey (RAL 7035) |  
 |  **IP degree of protection** |  IP23 conforming to IEC 61800-5-1 |  
 |  **Supply frequency** |  50/60 Hz +/- 5 % |  
 |  **[Us] rated supply voltage** |  380…415 V – 10…6 % |  
 |  **Network number of phases** |  3 phases |  
 |  **Output voltage** |  <= power supply voltage |  
 |  **Permissible temporary current boost** |  1.2 x In during 60 s (normal duty) | 1.5 x In during 60 s (heavy duty) |  
 |  **Speed drive output frequency** |  0.1…599 Hz |  
 |  **Continuous output current** |  1140 A at 2.5 kHz for normal duty | 900 A at 2.5 kHz for heavy duty |  
 |  **Power dissipation in W** |  16250 W, total (normal duty) | 12000 W, total (heavy duty) | 1800 W, control part (normal duty) | 1250 W, control part (heavy duty) |  
 |  **Motor power kW** |  630 kW for normal duty | 500 kW for heavy duty |  
 |  **Frequency resolution** |  Display unit: 0.1 Hz | Analog input: 0.012/50 Hz |  
 |  **Maximum switching current** |  Relay output R1 on resistive load, cos phi = 1: 3 mA at 250 V AC | Relay output R1 on resistive load, cos phi = 1: 3 mA at 30 V DC | Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 mA at 250 V AC | Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 mA at 30 V DC | Relay output R2, R3 on resistive load, cos phi = 1: 5 mA at 250 V AC | Relay output R2, R3 on resistive load, cos phi = 1: 5 mA at 30 V DC | Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 mA at 250 V AC | Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 mA at 30 V DC |  
 |  **Minimum switching current** |  Relay output R1, R2, R3: 5 mA at 24 V DC |  
 |  **Switching frequency** |  2…8 kHz adjustable with derating factor |  
 |  **Nominal switching frequency** |  2.5 kHz |  
 |  **Line current** |  1058 A at 400 V (normal duty) | 849 A at 400 V (heavy duty) |  
 |  **Apparent power** |  733 kVA at 400 V (normal duty) | 588 kVA at 400 V (heavy duty) |  
 |  **Maximum transient current** |  1368 A during 60 s per 10 min (normal duty) | 1350 A during 60 s per 10 min (heavy duty) |  
 |  **Net weight** |  850 kg |  
 |  **Overvoltage category** |  III |  
 |  **Package 1 Weight** |  890 kg |

### Downloads

 * [📥 User guide](https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=ATV900_Programming_Manual_EN_NHA80757_13.pdf&p_Doc_Ref=NHA80757)