# variable speed drive, Altivar Process ATV900, ATV950, 55kW, 75hp, 380 to 480V, IP55, UL type 12

- Link: https://danfossexpress.com/product/variable-speed-drive-altivar-process-atv900-atv950-55kw-75hp-380-to-480v-ip55-ul-type-12/
- Published: 2026-02-17T13:04:00+00:00
- Author: drivesexperts

## variable speed drive, Altivar Process ATV900, ATV950, 55kW, 75hp, 380 to 480V, IP55, UL type 12

**Manufacturer:** Schneider Electric

**Part Number:** ATV950D55N4U

### Key Specifications

 |  **Range of Product** |  Altivar Process ATV900 |  
 |  **Phase** |  3 phase |  
 |  **Mounting Mode** |  Wall mount |  
 |  **Continuous output current** |  106 A 2.5 kHz normal duty | 88 A 2.5 kHz heavy duty |  
 |  **[Us] rated supply voltage** |  380…480 V |  
 |  **Relative symmetric mains voltage tolerance** |  10 % |  
 |  **Relative symmetric network frequency tolerance** |  5 % |  
 |  **nominal output current** |  106.0 A |  
 |  **Motor power kW** |  55.0 kW normal duty | 45.0 kW heavy duty |  
 |  **IP degree of protection** |  IP55 |  
 |  **Maximum switching current** |  Relay output R1 resistive, cos phi = 1 3 A 250 V AC | Relay output R1 resistive, cos phi = 1 3 A 30 V DC | Relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC | Relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC | Relay output R2, R3 resistive, cos phi = 1 5 A 250 V AC | Relay output R2, R3 resistive, cos phi = 1 5 A 30 V DC | Relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC | Relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC |  
 |  **Minimum switching current** |  Relay output R1, R2, R3 5 mA 24 V DC |  
 |  **Maximum output frequency** |  599 Hz |  
 |  **Switching frequency** |  1…8 kHz adjustable | 2.5…8 kHz with derating factor |  
 |  **Nominal switching frequency** |  2.5 kHz |  
 |  **Line current** |  97.2 A 380 V normal duty) | 81.4 A 380 V heavy duty) | 84.2 A 480 V normal duty) | 71.8 A 480 V heavy duty) |  
 |  **Maximum Input Current per Phase** |  97.2 A |  
 |  **Maximum output voltage** |  480.0 V |  
 |  **Apparent power** |  70 kVA 480 V normal duty) | 59.7 kVA 480 V heavy duty) |  
 |  **Maximum transient current** |  127.2 A 60 s normal duty) | 132 A 60 s heavy duty) |  
 |  **Network Frequency** |  50-60 Hz |  
 |  **Base load current at high overload** |  88.0 A |  
 |  **Base load current at low overload** |  106.0 A |  
 |  **Net Weight** |  191.8 lb(US) (87 kg) |  
 |  **Overvoltage category** |  III |  
 |  **Package weight(Lbs)** |  235.9 lb(US) (107.0 kg) |

### Downloads

 * [📥 User guide](https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=ATV930_950_Installation_manual_EN_NHA80932_11.pdf&p_Doc_Ref=NHA80932)