# Variable speed drive, Altivar Process ATV900, APM, Low Harmonic/Regen 500 V, 220 kW

- Link: https://danfossexpress.com/product/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-500-v-220-kw/
- Published: 2026-02-16T15:50:03+00:00
- Author: drivesexperts

## Variable speed drive, Altivar Process ATV900, APM, Low Harmonic/Regen 500 V, 220 kW

**Manufacturer:** Schneider Electric

**Part Number:** ATV9B0C31N6

### Key Specifications

 |  **Range of product** |  Altivar Process ATV900 |  
 |  **Mounting mode** |  Cabinet mount |  
 |  **IP degree of protection** |  IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 | IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529 |  
 |  **Supply frequency** |  50…60 Hz +/- 5 % |  
 |  **Network number of phases** |  3 phases |  
 |  **[Us] rated supply voltage** |  500 V – 10…15 % |  
 |  **Permissible temporary current boost** |  1.2 x In during 60 s (normal duty) | 1.5 x In during 60 s (heavy duty) |  
 |  **Speed drive output frequency** |  0.1…599 Hz |  
 |  **Nominal switching frequency** |  2.5 kHz |  
 |  **Switching frequency** |  2…4.9 kHz adjustable with derating factor |  
 |  **Motor power kW** |  220.0 kW at 500 V normal duty | 160.0 kW at 500 V heavy duty | 220.0 kW at 500 V normal duty regenerative mode | 160.0 kW at 500 V heavy duty regenerative mode |  
 |  **Line current** |  278.0 A at 500 V (normal duty) | 204.0 A at 500 V (heavy duty) | 231.0 A at 500 V regenerative mode (normal duty) | 167.0 A at 500 V regenerative mode (heavy duty) |  
 |  **Apparent power** |  241.0 kVA at 500 V normal duty | 176.0 kVA at 500 V heavy duty | 200.0 kVA at 500 V normal duty regenerative mode | 145.0 kVA at 500 V heavy duty regenerative mode |  
 |  **Continuous output current** |  340.0 A at 2.5 kHz normal duty | 275.0 A at 2.5 kHz heavy duty | 340.0 A at 2.5 kHz normal duty regenerative mode | 275.0 A at 2.5 kHz heavy duty regenerative mode |  
 |  **Maximum transient current** |  408.0 A during 60 s (normal duty) | 412.5 A during 60 s (heavy duty) | 408.0 A during 60 s regenerative mode (normal duty) | 412.5 A during 60 s regenerative mode (heavy duty) |  
 |  **Frequency resolution** |  Display unit: 0.1 Hz | Analog input: 0.012/50 Hz |  
 |  **Minimum switching current** |  Relay output R1, R2, R3: 5 mA at 24 V DC |  
 |  **Maximum switching current** |  Relay output R1 on resistive load, cos phi = 1: 3 A at 250 V AC | Relay output R1 on resistive load, cos phi = 1: 3 A at 30 V DC | Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC | Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC | Relay output R2, R3 on resistive load, cos phi = 1: 5 A at 250 V AC | Relay output R2, R3 on resistive load, cos phi = 1: 5 A at 30 V DC | Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC | Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |