# Variable Speed Drive, Altivar Process ATV600, ATV630, 5.5kW, 7.5hp, 380 to 480V, IP21, UL type 1 [TAA, BAA, BABA]

- Link: https://danfossexpress.com/product/variable-speed-drive-altivar-process-atv600-atv630-5-5kw-7-5hp-380-to-480v-ip21-ul-type-1-taa-baa-baba/
- Published: 2026-02-16T15:52:55+00:00
- Author: drivesexperts

## Variable Speed Drive, Altivar Process ATV600, ATV630, 5.5kW, 7.5hp, 380 to 480V, IP21, UL type 1 [TAA, BAA, BABA]

**Manufacturer:** Schneider Electric

**Part Number:** ATV630U55N4US

### Key Specifications

 |  **Range of Product** |  Altivar Process ATV600 |  
 |  **Mounting Mode** |  Wall mount |  
 |  **[Us] rated supply voltage** |  380…480 V |  
 |  **Relative symmetric mains voltage tolerance** |  10 % |  
 |  **Relative symmetric network frequency tolerance** |  5 % |  
 |  **nominal output current** |  12.7 A |  
 |  **IP degree of protection** |  IP21IEC 61800-5-1 | IP21IEC 60529 |  
 |  **Supply frequency** |  50…60 Hz – 5…5 % |  
 |  **Motor power kW** |  5.5 kW normal duty) | 4 kW heavy duty) |  
 |  **Maximum Horse Power Rating** |  7.5 hp normal duty | 5 hp heavy duty |  
 |  **Line current** |  10.4 A 380 V normal duty) | 9.1 A 480 V normal duty) | 8 A 380 V heavy duty) | 7.2 A 480 V heavy duty) |  
 |  **Continuous output current** |  12.7 A 4 kHz normal duty | 9.3 A 4 kHz heavy duty |  
 |  **Speed drive output frequency** |  0.1…500 Hz |  
 |  **Maximum switching current** |  Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC | Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC | Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC | Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC |  
 |  **Minimum switching current** |  Relay output R1, R2, R3 5 mA 24 V DC |  
 |  **Phase** |  3 phase |  
 |  **Output voltage** |  <= power supply voltage |  
 |  **Permissible temporary current boost** |  1.1 x In 60 s normal duty) | 1.5 x In 60 s heavy duty) |  
 |  **Frequency resolution** |  Display unit 0.1 Hz | Analog input 0.012/50 Hz |  
 |  **Power range** |  4…6 kW 380…440 V 3 phase | 4…6 kW 480…500 V 3 phase |  
 |  **Enclosure mounting** |  Wall mounted |  
 |  **Maximum output frequency** |  500 kHz |  
 |  **Switching frequency** |  2…12 kHz adjustable | 4…12 kHz with derating factor |  
 |  **Nominal switching frequency** |  4 kHz |  
 |  **Maximum Input Current per Phase** |  10.4 A |  
 |  **Maximum output voltage** |  480.0 V |  
 |  **Apparent power** |  7.6 kVA 480 V normal duty) | 6 kVA 480 V heavy duty) |  
 |  **Maximum transient current** |  14 A 60 s normal duty) | 14 A 60 s heavy duty) |  
 |  **Network Frequency** |  50-60 Hz |  
 |  **Base load current at high overload** |  9.3 A |  
 |  **Base load current at low overload** |  12.7 A |  
 |  **Power dissipation in W** |  Natural convection 36 W 380 V 4 kHz | Forced convection 145 W 380 V 4 kHz |  
 |  **Net Weight** |  10.4 lb(US) (4.7 kg) |  
 |  **Overvoltage category** |  III |  
 |  **Package weight(Lbs)** |  13.832 lb(US) (6.274 kg) |

### Downloads

 * [📥 User guide](https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=ATV600_Programming_Manual_EN_EAV64318_13.pdf&p_Doc_Ref=EAV64318)