# Variable speed drive, Altivar Process ATV600, ATV630, 22kW/30 hp, 500V/690 V, IP00

- Link: https://danfossexpress.com/product/variable-speed-drive-altivar-process-atv600-atv630-22kw-30-hp-500v-690-v-ip00/
- Published: 2026-02-16T15:50:58+00:00
- Author: drivesexperts

## Variable speed drive, Altivar Process ATV600, ATV630, 22kW/30 hp, 500V/690 V, IP00

**Manufacturer:** Schneider Electric

**Part Number:** ATV630D22Y6

**EAN:** 3606481325174

### Key Specifications

 |  **Range of product** |  Altivar Process ATV600 |  
 |  **Mounting mode** |  Wall mount |  
 |  **[Us] rated supply voltage** |  500…690 V |  
 |  **Relative symmetric mains voltage tolerance** |  10 % |  
 |  **Relative symmetric network frequency tolerance** |  5 % |  
 |  **nominal output current** |  29.0 A |  
 |  **IP degree of protection** |  IP00 conforming to IEC 61800-5-1 | IP00 conforming to IEC 60529 | IP20 (with kit VW3A9705) conforming to IEC 61800-5-1 | IP20 (with kit VW3A9705) conforming to IEC 60529 |  
 |  **Supply frequency** |  50…60 Hz – 5…5 % |  
 |  **Motor power kW** |  18.5 kW at 500 V (normal duty) | 15 kW at 500 V (heavy duty) | 22 kW at 690 V (normal duty) | 18.5 kW at 690 V (heavy duty) |  
 |  **Motor power hp** |  25 hp at 500 V normal duty | 20 hp at 500 V heavy duty | 30 hp at 690 V normal duty | 25 hp at 690 V heavy duty |  
 |  **Line current** |  27.6 A at 500 V (normal duty) | 26 A at 690 V (normal duty) | 23.2 A at 500 V (heavy duty) | 23 A at 690 V (heavy duty) |  
 |  **Continuous output current** |  29 A at 4 kHz for normal duty | 24 A at 4 kHz for heavy duty |  
 |  **Speed drive output frequency** |  0.1…500 Hz |  
 |  **Maximum switching current** |  Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC | Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC | Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |  
 |  **Minimum switching current** |  Relay output R1, R2, R3: 5 mA at 24 V DC |  
 |  **Network number of phases** |  3 phases |  
 |  **Output voltage** |  <= power supply voltage |  
 |  **Permissible temporary current boost** |  1.1 x In during 60 s (normal duty) | 1.5 x In during 60 s (heavy duty) |  
 |  **Frequency resolution** |  Display unit: 0.1 Hz | Analog input: 0.012/50 Hz |  
 |  **Enclosure mounting** |  Wall mounted |  
 |  **Maximum output frequency** |  500 kHz |  
 |  **Switching frequency** |  2…8 kHz adjustable | 4…8 kHz with derating factor |  
 |  **Nominal switching frequency** |  4 kHz |  
 |  **Maximum input current** |  27.6 A |  
 |  **Maximum output voltage** |  690.0 V |  
 |  **Apparent power** |  31.1 kVA at 690 V (normal duty) | 27.5 kVA at 690 V (heavy duty) |  
 |  **Maximum transient current** |  31.9 A during 60 s (normal duty) | 36 A during 60 s (heavy duty) |  
 |  **Network frequency** |  50…60 Hz |  
 |  **Base load current at high overload** |  24.0 A |  
 |  **Base load current at low overload** |  29.0 A |  
 |  **Power dissipation in W** |  Natural convection: 138 W at 500 V, switching frequency 4 kHz | Forced convection: 463 W at 500 V, switching frequency 4 kHz |  
 |  **Net weight** |  22 kg |  
 |  **Overvoltage category** |  III |  
 |  **Package 1 Weight** |  31.000 kg |

### Downloads

 * [📥 User guide](https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=ATV600_Programming_Manual_EN_EAV64318_13.pdf&p_Doc_Ref=EAV64318)