# VACON0100-3L-0006-2-hvac – Vacon frequency inverters Vacon 100 HVAC pump series

- Link: https://danfossexpress.com/product/vacon0100-3l-0006-2-hvac-vacon-frequency-inverters-vacon-100-hvac-pump-series/
- Published: 2026-05-06T09:11:35+00:00
- Author: drivesexperts

VACON 100 HVAC is an AC drive developed especially for heating, ventilation and 
air conditioning applications. It comes with a power range of 0.55-160 kW and for
supply voltages of 230 V, 400 V or 480 V. Designed specifically for the building
automation industry, VACON 100 HVAC can enhance pump, fan and compressor applications.
Easy installation and efficient, trouble-free operation mean that just about anyone
can commission VACON 100 HVAC with a speedy return on investment guaranteed. 

 * Enclosure classes IP21/Type 1 and IP54/Type 12
 * BMS controller with industrial ethernet and RS485 protocols
 * BACnet IP and Modbus TCP via Ethernet and Modbus RTU, Metasys N2 and BACnet MSTP
   via RS485 available as standard
 * EMC harmonics: EN 61000-3-12 compliant
 * IEC61800-5-1 (2007), UL 508 C safety approval
 * CE, UL, cUL approvals
 * Graphical HMI keypad
 * Built-in PID controller
 * Standard I/O and optional expansion cards
 * Real Time Clock with battery backup
 * No charge time during storage time
 * RoHS compliant, no electrolytic capacitors, no lead in the circuit boards

### Specifications

 |  Manufacturer: |  Vacon |  
 |  Series: |  Vacon 100 Hvac |  
 |  Model: |  VACON0100-3L-0006-2-hvac  |  
 |  Application: |  pumps / fans |  
 |  Capacity, kW: |  1,1 |  
 |  Current, А: |  6.6 |  
 |  Main power supply, V: |  208-240 |  
 |  Phase: |  3 |  
 |  Output frequency, Hz: |  0…..320  |  
 |  Enclosure: |  IP 21 (IP54-option)  |  
 |  Overload capacity, % per 1 min.: |  110 |  
 |  Acceleration time, sec: |  0,1-3000  |  
 |  Deceleration time, sec: |  0,1-3000  |  
 |  EMC filter: |  + |  
 |  Braking unit: |  + |  
 |  Analog input: |  2 |  
 |  Digital input: |  6 |  
 |  Analog output: |  1 |  
 |  Digital output: |  – |  
 |  Relay output: |  3 |  
 |  RS485 (Modbus RTU): |  + |  
 |  Starting torque: |  200% |  
 |  PID: |  PID – regulation |  
 |  V/f control mode: |  + |  
 |  Vector control with feedback: |  – |  
 |  Sensorless vector control: |  + |  
 |  Operation temperature, °С: |  -10……+40 |  
 |  Storage temperature, °С: |  -40……+70 |  
 |  Dimensions (W x H x D), mm: |  128х328х190  |  
 |  Weight, kg: |  6 |