# Soft starter, Altistart 480, 62A, 208 to 690V AC, control supply 110 to 230V AC

- Link: https://danfossexpress.com/product/soft-starter-altistart-480-62a-208-to-690v-ac-control-supply-110-to-230v-ac/
- Published: 2026-02-17T12:00:19+00:00
- Author: drivesexperts

## Soft starter, Altistart 480, 62A, 208 to 690V AC, control supply 110 to 230V AC

**Manufacturer:** Schneider Electric

**Part Number:** ATS480D62Y

**EAN:** 3606481089045

### Key Specifications

 |  **Range of product** |  Altivar Soft Starter ATS480 |  
 |  **Network number of phases** |  3 phases |  
 |  **Ue power supply voltage** |  208…690 V – 15…10 % |  
 |  **power supply frequency** |  50…60 Hz – 20…20 % |  
 |  **[Ie] rated operational current** |  Normal duty: 62.0 A (at <40 °C) |  
 |  **rated current in heavy duty** |  47.0 A at 40 °C for heavy duty |  
 |  **IP degree of protection** |  IP20 |  
 |  **Motor power kW** |  15.0 kW at 230 V in the motor supply line normal duty | 11.0 kW at 230 V in the motor supply line heavy duty | 30.0 kW at 400 V in the motor supply line normal duty | 22.0 kW at 400 V in the motor supply line heavy duty | 30.0 kW at 440 V in the motor supply line normal duty | 22.0 kW at 440 V in the motor supply line heavy duty | 37.0 kW at 500 V in the motor supply line normal duty | 30.0 kW at 500 V in the motor supply line heavy duty | 37.0 kW at 525 V in the motor supply line normal duty | 30.0 kW at 525 V in the motor supply line heavy duty | 45.0 kW at 660 V in the motor supply line normal duty | 37.0 kW at 660 V in the motor supply line heavy duty | 45.0 kW at 690 V in the motor supply line normal duty | 37.0 kW at 690 V in the motor supply line heavy duty | 30.0 kW at 230 V to the motor delta terminals normal duty | 22.0 kW at 230 V to the motor delta terminals heavy duty | 55.0 kW at 400 V to the motor delta terminals normal duty | 45.0 kW at 400 V to the motor delta terminals heavy duty |  
 |  **Motor power hp** |  15.0 hp at 208 V normal duty | 20.0 hp at 230 V normal duty | 15.0 hp at 230 V heavy duty | 40.0 hp at 460 V normal duty | 30.0 hp at 460 V heavy duty | 50.0 hp at 575 V normal duty | 40.0 hp at 575 V heavy duty |  
 |  **[Us] control circuit voltage** |  110…230 V AC 50/60 Hz – 15…10 % |  
 |  **Apparent power** |  0.09 kVA |  
 |  **current limiting %In (5 x Ie maximum)** |  150…700 % |  
 |  **Rated current pwr loss specification** |  62.0 A |  
 |  **Power loss static current independent** |  25.0 W |  
 |  **Power loss per device current dependent** |  181.0 W |  
 |  **[Uc] control circuit voltage** |  24 V DC |  
 |  **Minimum switching current** |  100 mA at 12 V DC for relay outputs |  
 |  **Maximum switching current** |  Relay outputs 2 A at 250 V AC | Relay outputs 2 A at 30 V DC |  
 |  **Net weight** |  8.3 kg |  
 |  **[Uimp] rated impulse withstand voltage** |  6 kV |  
 |  **[Ui] rated insulation voltage** |  690 V |  
 |  **Package 1 Weight** |  9.662 kg |  
 |  **Package 2 Weight** |  85.500 kg |

### Downloads

 * [📥 User guide](https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=ATS480-User-Manual-EN-NNZ85515-06.pdf&p_Doc_Ref=NNZ85515)