# NXA04605-A0T02SG-A8A2B5D2E9+FL25+LS60 – VACON® NXP Common DC Bus 309 kW, IP00, 380–500 V

- Link: https://danfossexpress.com/product/nxa04605-a0t02sg-a8a2b5d2e9fl25ls60/
- Published: 2025-05-06T10:57:22+00:00
- Author: drivesexperts

## NXA04605-A0T02SG-A8A2B5D2E9+FL25+LS60 overview

**NXA04605-A0T02SG-A8A2B5D2E9+FL25+LS60** is a VACON® NXP Common DC Bus active front-
end unit rated 309 kW (495 A continuous output current) for three-phase 380–500 
V mains supply. It is built in an IP00 enclosure, frame size FI10, measures 1032
× 239 × 552 mm (H × W × D) and weighs 100 kg net (101 kg packed).

Danfoss ordering number: 132H3878, EAN 5714853328512.

## Configuration

 * EMC category C4
 * Alphanumeric Keypad control panel
 * I/O: OPTA1 w.galv.isol 2AI&1AO

## Model code breakdown

What each part of NXA04605-A0T02SG-A8A2B5D2E9+FL25+LS60 means:

  |  Position |  Code |  Meaning |  
   |  Product Group |  NXA |  Active Front-End Unit |  
 |  Customized Drive |  +BM26 |  Vacon Dark Grey NXP |  
 |  Mechanical Modification |  S |  Standard air cooled drive |  
 |  Mains voltage |  5- |  380 – 500 Vac (465-800 Vdc) |  
 |  Current |  0460 |  460 Amp |  
 |  Control Keypad |  A |  Alpha-numeric display |  
 |  Enclosure |  0 |  IP00 |  
 |  EMC emission levels |  T |  IEC61800-3 for IT networks |  
 |  Brake Chopper |  0 |  No Brake |  
 |  Electrical Modification |  2 |  AFE module w/o LCL |  
 |  Card Modifications |  G- |  FiberConnection+Varnished PCB |  
 |  Shipping Package |  +GSCB |  Cardboard box as Shipping pack |  
 |  Warranty |  +WT01 |  Warranty 12/18 months |  
 |  Gland Plate Option |  +QGNO |  No conduit plate |  
 |  Option Slot A |  A8 |  OPTA1 w.galv.isol 2AI&1AO |  
 |  Option Slot B |  A2 |  2RO(NO/NC) |  
 |  Option Slot C |  B5 |  3RO(NO) |  
 |  Option Slot D |  D2 |  SysBus(1fiber), CAN-MonBus |  
 |  Option Slot E |  E9 |  2-port ethernet |  
 |  Firmware language package |  +FL25 |  US,FR,ES,PT;Americas |  
 |  Documentation Level |  +DPAP |  Paper manuals |  
 |  Documentation Lang. Preference |  +DLUK |  English |  
 |  System Firmware |  +FNP02 |  System software NXP |  
 |  Software license |  NONE |  no software license |  
 |  Application |  +ARFIFF02 |  AFE application NXA,NXI,NXP |  
 |  Parameter Set |  NONE |  none |  
 |  Motor Parameter Default |  +LS60 |  Default Motor frequency 60HZ |  
 |  Labeling options |  +LPC1 |  no additional labels |  
 |  CE Approval |  +GACE |  CE Approval |  
 |  UL Approval |  +GAUL |  UL approval |  
 |  RCM Approval |  +GACT |  RCM Approval N16307 |  
 |  Marine approval |  NONE |  no marine approval |  
 |  KC Approval |  +GAKC |  Korean Approval |  
 |  Ukrainian Approval |  +GAUA |  Ukrainian Approval |  
 |  EAC Approval |  +GAEA |  EAC Approval |

## Same configuration, other power sizes

 * [114 kW: NXA01685-A0T02SG-A8A2B5D2E9+FL25+LS60](https://danfossexpress.com/product/nxa01685-a0t02sg-a8a2b5d2e9fl25ls60/)

Need a price or lead time for NXA04605-A0T02SG-A8A2B5D2E9+FL25+LS60? Send the model
code or ordering number with your quantity and delivery country, and we will reply
with a quotation. See [how to request a quote](https://danfossexpress.com/how-to-request-a-quote/).