# IC7-60FA3N05-12A5E20F1+ACBC+ALDC+BAMT+BDBA+BEF1+BF20+DAAU – iC7-Automation Frequency Converter 5.5 kW / 7.5 HP, IP20, 380–500 V

- Link: https://danfossexpress.com/product/ic7-60fa3n05-12a5e20f1acbcaldcbamtbdbabef1bf20daau/
- Published: 2025-05-06T08:23:34+00:00
- Author: drivesexperts

## IC7-60FA3N05-12A5E20F1+ACBC+ALDC+BAMT+BDBA+BEF1+BF20+DAAU overview

**IC7-60FA3N05-12A5E20F1+ACBC+ALDC+BAMT+BDBA+BEF1+BF20+DAAU** is a iC7-Automation
Frequency Converter rated 5.5 kW / 7.5 HP (12.5 A continuous output current) for
three-phase 380–500 V mains supply. It is built in an IP20/Open Type enclosure, 
frame size FA02a, measures 270 × 90 × 221 mm (H × W × D) and weighs 4.57 kg net (
5.748 kg packed).

Danfoss ordering number: 132X3404, EAN 5715253183077. Power loss at rated load is
175 W.

## Configuration

 * RFI filter Class A1/B (EMC category C1)
 * Built-in brake chopper
 * Safe Torque Off (STO)
 * Control Panel 2.8 (OPX20)
 * Fieldbus: Modbus TCP OS7MT
 * I/O: 4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO

## Model code breakdown

What each part of IC7-60FA3N05-12A5E20F1+ACBC+ALDC+BAMT+BDBA+BEF1+BF20+DAAU means:

  |  Position |  Code |  Meaning |  
   |  Product series |  +DAAU |  iC7-Automation |  
 |  Product group |  IC7-60 |  iC7-60 |  
 |  Product category |  FA |  Frequency converter,air-cooled |  
 |  Product type |  3N |  3~ |  
 |  Mains voltage |  05 |  380-500 V AC |  
 |  Current rating |  -12A5 |  12.5 A |  
 |  Power rating |  5K5 |  5.5 kW/7.5 hp |  
 |  Protection rating |  E20 |  IP20/Open Type |  
 |  EMC category |  F1 |  C1 and C2 category |  
 |  Cable entry and EMC plate |  +AAST |  Standard plate |  
 |  Integrated brake chopper |  +ACBC |  Yes |  
 |  Extra environmental protection |  +AGXX |  None |  
 |  Humidity protection device |  +AHXX |  None |  
 |  Integrated common-mode filter |  +AIXX |  None |  
 |  Mains input device |  +AJXX |  None |  
 |  DC terminals |  +ALDC |  Yes |  
 |  Touch protection |  +AMXX |  None |  
 |  Heat sink access panel |  +APXX |  None |  
 |  Communication interface, X1/X2 |  +BAMT |  Modbus TCP OS7MT |  
 |  Communication interface, X0 |  +BBEL |  Ethernet port, no protocol |  
 |  Standard I/O |  +BDBA |  4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO |  
 |  Functional safety |  +BEF1 |  STO, not upgradable |  
 |  Control panel |  +BF20 |  Control Panel 2.8 OPX20 |  
 |  Interface board |  +BISR |  MicroSD card reader and RTC |  
 |  Option slot A |  +CAX0 |  None |  
 |  Option slot B |  +CBXX |  None, not upgradable |  
 |  Option slot C |  +CCX0 |  None |  
 |  Option slot D |  +CDX0 |  None |  
 |  Option Slot E |  +CEX0 |  None |  
 |  Customer specific application |  +DBXX |  None |  
 |  Additional drive features 1 |  +DD1X |  None |  
 |  Additional drive features 2 |  +DE2X |  None |  
 |  Additional drive features 3 |  +DF3X |  None |  
 |  Additional drive features 4 |  +DG4X |  None |  
 |  Additional drive features 5 |  +DH5X |  None |  
 |  High speed enabled |  +DI6X |  No |  
 |  Customization file package ID |  +EAXXXXXX |  No customization |  
 |  Product software ID |  +ECXXX |  Latest released version |  
 |  Technical documentation |  +EGIN |  Installation guide |  
 |  Customer-specific label |  +EJXX |  None |

Need a price or lead time for IC7-60FA3N05-12A5E20F1+ACBC+ALDC+BAMT+BDBA+BEF1+BF20
+DAAU? Send the model code or ordering number with your quantity and delivery country,
and we will reply with a quotation. See [how to request a quote](https://danfossexpress.com/how-to-request-a-quote/).