# FC-302P75KT5P55H5XGCXXXSXXXXAXBXCXXXXDX

- Link: https://danfossexpress.com/product/fc-302p75kt5p55h5xgcxxxsxxxxaxbxcxxxxdx/
- Published: 2025-05-06T09:12:22+00:00
- Author: drivesexperts

Frequency converter
FC-302P75KT5P55H5XGCXXXSXXXXAXBXCXXXXDX

VLT® AutomationDrive FC-302
(P75K) 75 KW / 100 HP, Three phase, 380 – 500 VAC,IP55/
Type12 BackplateMarine,ruggedis RFI A2(C3)No brake chopperGraphical Loc. Cont. PanelCoated
PCB, No Mains OptionLatest release std. SW.Frame: C2No A Option, No B OptionNo C1
option, No D option

Other options according to Model code

 **
 Model code:  FC-302P75KT5P55H5XGCXXXSXXXXAXBXCXXXXDX

The VLT® AutomationDrive represents a single drive concept that controls the entire
range of operations from ordinary to servo like applications on any machine or production
line.

  |  **Gross weight** |    |   60.67 Kilogram |    |  
 |  **Net weight** |    |   57.33 Kilogram |    |  
 |  **Volume** |    |   232.653 Liter |    |  
 |  **EAN** |    |   5710107413232 |    |

###   

  |  **Product View (Switch)** |   GLBL |   Global (Standard) |    |  
 |  **Product Group** |   FC- |   VLT® AutomationDrive FC- |    |  
 |  **Series** |   302 |   302 |    |  
 |  **Power Rating** |   P75K |   (P75K) 75 KW / 100 HP |    |  
 |  **Phase** |   T |   Three phase |    |  
 |  **Mains Voltage** |   5 |   380 – 500 VAC |    |  
 |  **Enclosure** |   P55 |   IP55 / Type12 Backplate |    |  
 |  **RFI Filter** |   H5 |   Marine,ruggedis RFI A2(C3) |    |  
 |  **Brake – Safe Stop** |   X |   No brake chopper |    |  
 |  **LCP** |   G |   Graphical Loc. Cont. Panel |    |  
 |  **Coating PCB** |   C |   Coated PCB |    |  
 |  **Mains Option** |   X |   No Mains Option |    |  
 |  **Adaptation A** |   X |   Standard Cable Entries |    |  
 |  **Adaptation B** |   X |   No adaptation |    |  
 |  **Software Release** |   SXXX |   Latest release std. SW. |    |  
 |  **Software Language Pack** |   X |   Standard Language Pack |    |  
 |  **A Option** |   AX |   No A Option |    |  
 |  **B Option** |   BX |   No B Option |    |  
 |  **C0 Option MCO** |   CX |   No C0 option |    |  
 |  **C1 Option** |   X |   No C1 option |    |  
 |  **C Option Software** |   XX |   No software option |    |  
 |  **D Option** |   DX |   No D option |    |  
 |  **Frame Size** |   C2 |   C2 |    |  
 |  **Typecode Part 1** |    |   FC-302P75KT5P55H5XGC |    |  
 |  **Typecode Part 2** |    |   XXXSXXXXAXBXCXXXXDX |    |  
 |  **Product Catalog** |   NO_VIEW |   NO VIEW |    |  
 |  **Power 150% (HO) [KW]** |   75 |   75 |    |  
 |  **Power 110% (NO) [KW]** |   90 |   90 |    |  
 |  **Height [mm]** |   780,0 |   780,0 |    |  
 |  **Width w/ no C options [mm]** |   370,0 |   370,0 |    |  
 |  **Depth [mm]** |   332,0 |   332,0 |    |  
 |  **Depth with Option A/B [mm]** |   332,0 |   332,0 |    |  
 |  **kVA** |   102 |   102 |    |  
 |  **Power Loss NO [W]** |   1474 |   1474 |    |  
 |  **Power Loss NO [W]** |   1474 |   1474 |    |  
 |  **Power Loss HO [W]** |   1232 |   1232 |    |  
 |  **Power Loss HO [W]** |   1232 |   1232 |    |  
 |  **Continuous Current (NO) [A]** |   177 |   177 |    |  
 |  **Intermittent Current (NO) [A]** |   195 |   195 |    |  
 |  **Continuous Current (NO) [A]** |   160 |   160 |    |  
 |  **Intermittent Current (NO) [A]** |   176 |   176 |    |  
 |  **Continuous Current (HO) [A]** |   147 |   147 |    |  
 |  **Intermittent Current (HO) [A]** |   220 |   220 |    |  
 |  **Continuous Current (HO) [A]** |   130 |   130 |    |  
 |  **Intermittent Current (HO) [A]** |   195 |   195 |    |  
 |  **Calculated Gross Weight [kg]** |    |   60.67 |    |  
 |  **Calculated Net Weight [kg]** |    |   57.33 |    |  
 |  **ECCN EU** |   Y901 |   Y901 |    |  
 |  **ECCN US** |   3A999.a |   3A999.a |    |  
 |  **DrivePro category** |   EXCH |   Exchange Unit |    |